Preview

Voltage Sag And Swell Case Study

Powerful Essays
Open Document
Open Document
1345 Words
Grammar
Grammar
Plagiarism
Plagiarism
Writing
Writing
Score
Score
Voltage Sag And Swell Case Study
found in the literature. These problems have become one of the major concern, especially, with the use of power electronics devices which are sensitive to the variation of power supply. Among these problems Voltage Sag & Swell are identified as major concern to the electrical consumers. Voltage Sag is one of the most occurring power quality problems that cause severe problems and losses to industry. With the power systems restructuring and shifting trend towards distributed and dispersed generation, the concern of power quality has taken newer dimensions. In developing countries like India, where the variation of power frequency and many such other problems related to power quality are themselves a serious question, it is very vital to take …show more content…
These devices are modeled using PI controller and Discrete PWM pulse generator. The simulations were performed using MATLAB/SIMULINK using SIMPOWER SYSTEM.
Keywords: DSTATCOM (Distribution Static Compensator), Power Quality, DVR (Dynamic Voltage Restorer), Sag, VSC(Voltage Source Converter), PWM
I. INTRODUCTION
Voltage sag, voltage swell and momentary power loss are seen as vital issues from the last decade due to the widespread use of sophisticated power electronic equipment. Due to this the loads are becoming more sensitive and less tolerant to short term voltage disturbances in the form of voltage sag and voltage swell. A great effort has been made to enhance the power quality either
…show more content…
The DVR consists of solid state power electronics switching device either GTO or IGBT, energy storage device and injection transformers. It can maintain load voltage by injecting three phase output voltages whose phase, magnitude and frequency can be controlled [2]. The converter generates the reactive power needed while the taking active power from the energy storage. The energy storage can be different depending on the needs of compensating. The DVR often has limitations on the depth and duration of the voltage sag that it can compensate. The DVR expected time response is about 25millisecond and which is less than some of the traditional methods of voltage correction such as tap-changing transformer. Fig.2. Schematic diagram of DVR

Energy storage device becomes one of the constraint factors in the distribution compensation process, especially for sag and long duration fault due to its capacity. The load impedance Zth depends on the fault level of the load bus. When the system voltage (Vth) drops, the DVR injects a series voltage VDVR through the injection transformer so that the desired load voltage magnitude VL can be maintained. The series injected voltage of the DVR can be written as:

VDVR= VL + Zth IL - Vth (3)
Where, VL: The desired load voltage magnitude; Zth: The load impedance;

You May Also Find These Documents Helpful

  • Satisfactory Essays

    Dc-Dc Converter

    • 1381 Words
    • 6 Pages

    • • • • • • What is Power Electronics? Applications of power electronics. Linear vs Switched power conversion. Switching‐power pole Inductors and capacitors‐basic properties. Pulse‐Width‐Modulation (PWM)…

    • 1381 Words
    • 6 Pages
    Satisfactory Essays
  • Powerful Essays

    Shunt capacitor banks (SCB) are mainly installed to provide capacitive reactive compensation/ power factor correction. The use of SCBs has increased because they are relatively inexpensive, easy and quick to install and can be deployed virtually anywhere in the network. Its installation has other beneficial effects on the system such as:…

    • 7024 Words
    • 29 Pages
    Powerful Essays
  • Powerful Essays

    Each load connected to the feeder can now be modeled. To accurately simulate the voltage profile, three types of loads will be modeled. These include a constant current load, a constant impedance load, and a load with constant real and reactive power. To simplify needed calculations, each delta-connected load shall be converted to a wye-connected load using Equation (2).…

    • 1240 Words
    • 5 Pages
    Powerful Essays
  • Good Essays

    Real power reserves will then be further discussed. Reserve is categorized into two, normal operation reserve and disturbance reserve at which it is dependent on the cause of the reserve requirement. It is based on how fast the reserve capacity is available for the system operation. Firstly, the instantaneous reserve consists of frequency control reserve and momentary disturbance reserve, at which available within 30 sec. Frequency control reserve keeps the frequency within tolerance ± 0.1 Hs where used frequency control reserve is after 15mins replaced by fast reserve. Furthermore, momentary disturbance reserve replaces the lost production of tripped units or outages of important transmission lines. The same goes to momentary disturbance reserve at which 15mins is needed for replacing with fast disturbance reserve. NORDEL has PD1b with 200 MW less than the decisive fault case, relying on the consumption, frequency and voltage…

    • 949 Words
    • 4 Pages
    Good Essays
  • Powerful Essays

    Protection Course over View

    • 14947 Words
    • 60 Pages

    They may occupy different angular positions, but all machines rotate at the same electrical speed. This close…

    • 14947 Words
    • 60 Pages
    Powerful Essays
  • Powerful Essays

    As a result of reforms in the power sector many new Distribution Companies have started their operations. Apart from improving financial viability, reduction of T&D losses the distribution reforms have been identified as a key area in terms for fulfilling consumers‘ expectations in terms of service delivery in the area of Reliability and Quality of power supply. Reliability and Quality of power supply were rarely an issue till recent past and little or no attention was paid to these aspects of power supply. If consumers‘ expectations are not fulfilled in respect of Reliability and Quality of power supply there is resentment and they are reluctant to pay for the service. On the other hand if the expectations are met or surpassed the consumers are satisfied and willingness to pay increases by sharing the tariff hike. This in turn helps to tone up the financial viability of the DISCOMs (Distribution Companies). Reliability has to do with continuous and uninterrupted power supply i.e. total loss of voltage. Reliability does not cover voltage sags, swells, impulses or harmonics. Reliability indices typically consider such aspects as –     Number of consumers Connected load Duration of the interruptions measured Quantum of power interrupted and…

    • 2760 Words
    • 12 Pages
    Powerful Essays
  • Good Essays

    The fault analysis for full load condition has been done for input DC voltage 460 V, 470 V and 480 V when the slip set at 0.08. The obtained power spectrums of faulty conditions have been compared with healthy power spectrums(Fig.4 and Fig.5). It has clrealy been observed that the healthy and faulty stator power spectrums are dis-simlilar from each other. It has also been observed that if the fault severity increased then the side lobes around the fundamental frequency has also been getting increased. It may be shown in Fig.5.…

    • 848 Words
    • 4 Pages
    Good Essays
  • Powerful Essays

    On the following pages is an example of a formatted paper which follows the guidelines set forth in Parts 2 and 3 of…

    • 1543 Words
    • 7 Pages
    Powerful Essays
  • Powerful Essays

    ABSTRACT: A PC based electricity power management system has been designed and constructed. The designed PC based electricity power management system were achieved by the use of a timer software which acts as a computer User Interface control and a hardware which acts as a computer interface with the help of a parallel port.…

    • 1834 Words
    • 8 Pages
    Powerful Essays
  • Better Essays

    The dynamic state estimation based protection (also known as setting-less protection) has been inspired from the differential protection function and can be considered as an extension and generalization as illustrated in Figure 1. In current differential protection the electric currents at all terminals of a protection zone are measured and their weighted sum must be equal to zero (generalized Kirchhoff’s current law). Thus the current differential protection function consists of measuring the sum of the currents and as long as it is zero or near zero no action is taken. In dynamic state estimation based protection, all existing measurements in the protection zone are utilized. These measurements include: currents and voltages at the terminals of the protection zone, currents and voltages inside the protection zone (as in capacitor bank protection), speed and torque (as in rotating machinery), or other internal measurements including thermal measurement. All above measurements should obey the physical laws for the protection zone (physical laws such as KCL, KVL, motion laws and thermodynamic laws). The physical laws of the protection zone are captured in the dynamic model of the protection zone.…

    • 1166 Words
    • 5 Pages
    Better Essays
  • Better Essays

    The Nonlinear devices, like power electronics converters, induction motors, arc furnaces, etc. inject harmonic currents in the AC system which increase overall reactive power demanded by the equivalent load. Also, the number of sensitive loads that require ideal sinusoidal supply voltage for their proper operation has increased. In order to keep power quality under limits proposed by standards, different compensating techniques using series and shunt active filters have been proposed. Active power Filter (APF) characteristics depends on the accuracy of reference/extracted signal and its speed of computation. Different schemes such as Fast Fourier Transform (FFT), Kalman filter, Instantaneous Reactive Power (IRP) and Synchronous Reference Frame (SRF) theory, for the extraction of the desired signal…

    • 1648 Words
    • 7 Pages
    Better Essays
  • Better Essays

    The DVR shown in Fig. 3.1 is based on an inverter system that has energy storage for supplying active power, an output filter to make more sinusoidal voltage, and a step up transformer. The DVR is one of the FACTS devices that use the power electronics technology, especially inverter technology and is configured as a series-connected voltage controller. To control the output voltage of the DVR, the inverter supplies the missing load voltage using self-commutable electronic switches such as a gate turn-off thyristor (GTO), an insulated gate bipolar transistor (IGBT), or an insulated gate commutated thyristor (IGCT). The DVR injects the missing voltage in a series. Therefore, it can be called a series voltage controller, but the term DVR is commonly used now. DVRs have a same configuration of SSSC. The DVRs can be operated with a relatively small capacitor to exchange reactive power or can supply active powers to loads with energy storage. The large capacitor bank, flywheel, superconducting magnetic device, and battery can be used for the energy storage. The DVR, located between the supply and critical loads, has demonstrated excellent dynamic capability for mitigating voltage sags or swells. Each phase can be controlled independently, and the DVR can adjust the…

    • 1143 Words
    • 5 Pages
    Better Essays
  • Good Essays

    Power Supply Regulation

    • 1046 Words
    • 5 Pages

    DC-DC voltage converters are often used to provide a regulated voltage supply from an unregulated voltage source. Unregulated voltage sources can be rectified line voltages that exhibit fluctuations due to changes in magnitude. Regulated voltage supplies provide an average DC output voltage at a desired level (3.3 V, 2.5 V, etc.), despite fluctuating input voltage sources and variable output loads. Factors to consider when deciding on a regulated voltage supply solution include:…

    • 1046 Words
    • 5 Pages
    Good Essays
  • Powerful Essays

    This paper focus on the first two of these requirements. Choosing the type of FACTS devices and deciding the installation location and control of FACTS. We presented a simple algorithm based in heuristic and practical rules to seek the optimal location of two types of FACTS, shunt compensation ‘SVC’ and series compensation ‘TCSC’. The system loadability and loss minimization are applied as a measure of power system performance. Results show the impact of optimal operating points of FACTS (SVC and TCSC) devices under various conditions of power system.…

    • 2992 Words
    • 12 Pages
    Powerful Essays
  • Good Essays

    Electrical Protection

    • 381 Words
    • 2 Pages

    We thank Sri B.Babu, Special Officer (Protection), Sri Vivekananda and Sri Sachidanandam, Divisional Engineers, APGENCO, Sri M.Gopal Rao, Chief Engineer, Sri L.M.Sastry and Sri J.Dakshina Murthy, Superintending Engineers, APTRANSCO for their valuable advise in preparation of this book. We also thank Sarvasri G. Seshagiri Rao, Divisional Engineer, M.Jagan Mohan Rao, Assistant Divisional Engineer, K.Srinivasa Rao, V.Venkateswarlu and Mrs.Shilpa, Assistant Engineers of APTRANSCO, Sri V.R.Rao and Sri Diganta of PGCIL for patiently going through the Hand Book and for their valuable suggestions in bringing out this Book. We specially thank Dr.Bhuvanaika Rao, APGENCO for his contribution of the chapter on Excitation & Voltage Control. Our special thanks to Sri M. Sreenivasa Reddy and Sri A.Bhaskar J.P.Os who has…

    • 381 Words
    • 2 Pages
    Good Essays