Single Family Dwelling
The dwelling has 19 lighting outlet and 12 convenience outlet. It has the typical household appliances including one 8-kw electric range, two 1.5-hp room air conditioning unit, one 2.5 kw water heater, one laundry washing machine.

Lighting Layout

Power Layout

Lighting and Power Panel|
CircuitNo.| Description| No. of Outlet| Volts| Watts| Phase Current| Circuit Breaker| Conductor size (mm2)| Size of Conduct| | | | | | | AT| AF | P| | |
1| Lighting| 10| 230| 1000| 4.35| 15| 50| 2| 2.0mm2 TW + GND| 15 mm Ø Conduit pipe| 2| Lighting| 9| 230| 900| 3.91| 15| 50| 2| 2.0mm2 TW + GND| 15 mm Ø Conduit pipe| 3| Receptacle (C.O)| 6| 230| 1080| 4.69| 20| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 4| Receptacle (C.O)| 6| 230| 1080| 4.69| 20| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 5| 1.5 HP Aircon| 1| 230| 2300| 10.00| 30| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 6| 1.5 HP Aircon| 1| 230| 2300| 10.00| 30| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 7| Water Heater| 1| 230| 2500| 10.86| 20| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 8| Laundry| 1| 230| 1500| 6.52| 20| 50| 2| 3.5mm2 TW + GND| 15 mm Ø Conduit pipe| 9| Electric Range| 1| 230| 8000| 34.78| 40| 50| 2| 8.0mm2 TW + GND| 20 mm Ø Conduit pipe| 10| Spare| -| 230| -| -| 40| 50| 2| -| -|

Schedule of Loads
IT= 89.8 + 0.25% (10) x 0.8 D.F.
=73.86A
* Use 2-30mm2 THW Copper Wire and 1-22mm2 THW Copper Wire in 32mm Ø Conduit Pipe * Use 100 AMP 2-Pole Circuit Breaker 230 Volts
Single Line Diagram

Electrical System Design Layout

Submitted to:
Engr. Raymund C. Ycay

Submitted by:
Villanueva, Joshua Francis A.
BSIE III-2

Lighting and Power Panel|
CircuitNo.| Description| No. of Outlet| Volts| Watts| Phase Current| Circuit Breaker| Conductor size (mm2)| Size of Conduct| | | | | | | AT...
tracking img