Resistance Temp Detector
2012

RTDs
Temperature Measurements
Anshul Sharma
2010A8PS255P
Wasim Sajid
2010A8PS253P
Suman Saurav Giri 2010A8PS256P in partial fulfillment of the course

Transducers and Measurement Systems

Submitted To :

Prof. Surekha Bhanot
Department Of Electronics and Instumentation
Bits Pilani

Birla Institute Of Technology And Science
Pilani, Rajasthan. 333031

E&I
10/11/2012

2

Acknowledgements
First and foremost, we would like to thank God for supporting us always. We express our heartfelt gratitude towards Prof.
Surekha Bhanot, Instrumentation Chief for providing us with such a learning opportunity. We would also like to thank Mr.
Rajesh Purohit for taking out time to provide the material without which compilation of this report would not have been possible. We are thankful to Mr. Parikshit K Singh for guiding us in this course. A sincere gratitude towards our friends for their genuine interest in the report, valuable inputs, patience and constructive criticism. We take this opportunity to thank the entire staff of Department of Electronics and
Instrumentation to provide us with valuable inputs for the study. We express our heartfelt gratitude towards the
Instrumentation Forum for helping us with materials for this study. We thank BITS Pilani for giving us the opportunity to gain practical exposure so early in our careers. And lastly, we would like to thank our senior, Priyank Devpura for helping us to research on this topic and directing and supporting us at every step in this endeavor.

E&I | BITS Pilani

3

Abstract
The Report covers the experience gained in the completion of the TMS project under the Department of Electronics and
Instrumentation, Bits Pilani. The cooperating teachers and experienced staff has added to the entire experience of the learning. The report covers the basics of Resistance Temperature
Detectors (RTDs) and their characteristics. The report also discusses about RTDs in Bridge

You May Also Find These Documents Helpful

  • Good Essays

    6.03 Calorimetry Lab

    • 529 Words
    • 3 Pages

    Approximately 40 mL of the ionized water was added to the 100 mL beaker, then in a 10-mL graduated cylinder, 5-mL of HCl was measured then added to the 100-mL beaker of water. The 100 mL beaker was then placed on the assembled ring stand.…

    • 529 Words
    • 3 Pages
    Good Essays
  • Better Essays

    6.03 Calorimetry Lab

    • 1068 Words
    • 5 Pages

    This buffering ability is achieved via the equilibrium between the acid and its conjugated base in the reaction.…

    • 1068 Words
    • 5 Pages
    Better Essays
  • Good Essays

    6.03 Calorimetry Lab

    • 380 Words
    • 2 Pages

    Class average for a 80 and 120 drop count was recorded to be 0.041+/- 0.005 mL/drop. If a graduated cylinder is not available there is another way of adding more of the solution. The disposable pipet can transfer 0.5mL of the solution to the chemical reaction. When comparing a 10mL graduated cylinder, a 100mL beaker, and a 50mL graduated cylinder, the most precision peace of glass wear would be the 10 mL graduated cylinder with the true volume of water (calculated), class average, and uncertainties being 9.7896 +/- 0.05mL. The 50mL graduated cylinder comes in second place with a true volume of water(calculated), class average, and uncertainties being 50.0001 +/- 0.22mL. The third peace of glassware coming in as the least accurate would be the 100 mL beaker with a true volume of water(calculated), class average, and uncertainties being 59.9999 +/- 0.82mL.…

    • 380 Words
    • 2 Pages
    Good Essays
  • Good Essays

    6.03 Calorimetry Lab

    • 356 Words
    • 2 Pages

    Add 50 milliliters of the solution you want to test to the beaker and record its mass. The mass of the solution is equal to the total mass minus the mass of the beaker.…

    • 356 Words
    • 2 Pages
    Good Essays
  • Satisfactory Essays

    Lab 40 Calorimetry

    • 490 Words
    • 2 Pages

    Calorimetry is the measurement of the quantity of heat exchanged during chemical reactions or physical changes. For example, if the energy from an exothermic chemical reaction is absorbed in a container of water, the change in temperature of the water provides a measure of the amount of heat added.…

    • 490 Words
    • 2 Pages
    Satisfactory Essays
  • Good Essays

    The purpose of this lab is to determine an accurate time when the ice completely melts and the water starts to boil. The problem is which type of temperature change will result from heating ice to liquid, then boil (steam)? What will happen to the water after the boil? I hypothesise the water heats ice to liquid and then goes to simmer and boil. The independent variable is the hot plate changed to a burner itself. The dependent variable is what we are measuring is the time.…

    • 504 Words
    • 3 Pages
    Good Essays
  • Powerful Essays

    Specific Heat Lab

    • 1793 Words
    • 8 Pages

    Specific heat and climate were the primary focus of this lab. Specific heat is defined as “the measure of the ability of a substance to change temperature”. The purpose for carrying out this lab was to determine the specific heat/rates of both soil and water, and then comparing them. Students also were to relate specific heat to climate. Students were to determine which substance expressed a higher specific heat by using the formula, (q=m*Δt*c). Then they were to explain how specific heat and climate are in relation to one another.…

    • 1793 Words
    • 8 Pages
    Powerful Essays
  • Satisfactory Essays

    Boiling Point Lab

    • 529 Words
    • 3 Pages

    The purpose of this lab is to find the boiling point of the liquid and find the melting point of the solid.…

    • 529 Words
    • 3 Pages
    Satisfactory Essays
  • Better Essays

    In this experiment, the specific heat and the density of an unknown metal was determined in order to identify the unknown metal. The average specific heat of the unknown metal was 0.197˚C and was determined using a calorimeter. The density of the unknown metal was 6.57 g/mL and was determined using a cylinder and displacement. Using the specific heat value of the unknown metal and its density, it was determined that the unknown metal was Tin.…

    • 1030 Words
    • 5 Pages
    Better Essays
  • Good Essays

    Thermo Chem

    • 1327 Words
    • 6 Pages

    Suggest the main reason for the difference between this value and your calculated value in (a)(ii).[1]…

    • 1327 Words
    • 6 Pages
    Good Essays
  • Powerful Essays

    Begin our experiment by setting up the apparatus below; there are two Styrofoam cups (one inside another) and a thermometer clamp to hold the probe. Create a lid for the calorimeter using an inverted cup, cut in half and placing the cups on a…

    • 1419 Words
    • 6 Pages
    Powerful Essays
  • Good Essays

    In part A of the experiment the two values obtained for the specific heat capacity of the metal were about .0500 J/mol. This is a large deviation, with both of these values identifying very different metals. The average heat capacity identified the metal used as brass. The average heat capacity calculated was .3776 J/mol and the actual heat capacity of brass is .375 J/mol. The second run displayed the closest value to the actual value. A source of error that may have caused a large divide in the calculations could have been when the metal was transferred from the boiling water to the calorimeter. In the first run the metal was not fully submerged on the water from the calorimeter and was uncovered for more than two seconds. The second run was smoother in this section and displayed a value much closer to the actual specific heat capacity of the metal. This error can be prevented with a smoother transfer of the metal from the boiling water to the calorimeter with a pair of tongs that have a rubber tip that has a better grip of the metal.…

    • 500 Words
    • 2 Pages
    Good Essays
  • Good Essays

    • the study of how to produce low temperatures. • the study of what happens to materials when you’ve cooled them down.…

    • 7799 Words
    • 32 Pages
    Good Essays
  • Good Essays

    We measured the resistance per foot of a wire using setups of both two and four test leads in tandem with a digital voltmeter (DVM) and compared their accuracy. While resistance can be determined by measuring voltage and current separately, it can also be measured more simply and directly using the resistance measuring feature available to some digital voltmeters, such as the Agilent 34401A we employ here. Plugging two test leads into the DVM and placing them in series with the device under test (DUT) can be sufficient, but only if the DUT has a resistance of at least an order of magnitude larger than the internal and contact resistances within the leads. If one forgets about these resistances, they may be led to believe that two leads are always sufficient for accurate resistance measurements. A four-lead setup adds two more test leads that divert current flow from the original two, therefore eliminating the voltage drops caused by the leads’ internal resistances and their contact resistances with the DUT. Here, both setups were tried and their accuracy and practicality compared. A two-foot long 22 American Wire Gauge copper wire’s resistance per foot was measured to be 49.2 m/ft (206% from the accepted value of 16.1/ft) and 16.6 m/f (3.11% from the accepted value) using the two-wire and four-wire techniques, respectively.…

    • 526 Words
    • 2 Pages
    Good Essays
  • Good Essays

    Try all the problems previously assigned, look at the problems in your textbook, and try these:…

    • 737 Words
    • 3 Pages
    Good Essays