Preview

Lab Report on Reinforced Concrete Design

Powerful Essays
Open Document
Open Document
1463 Words
Grammar
Grammar
Plagiarism
Plagiarism
Writing
Writing
Score
Score
Lab Report on Reinforced Concrete Design
Introduction:
In this laboratory experiment, we were required to produce a concrete mixture based on the BRE Manual Design of concrete mixtures which is attached to this report. It is then used to produce concrete cubes and prisms.
The objective of this experiment is to learn the methods of producing concrete and concrete characteristics as well as comparing the theoretical values of the concrete’s Young’s Modulus with experimental values.

Procedure for concrete mix:
A concrete mix was designed based on the BRE Manual Design of concrete mixtures. Then, a total of 40kg of the required proportions of Ordinary Portland cement which includes water, fine aggregate, and 20mm size crushed gravel coarse aggregate was weighed out. The materials are then batched and mixed in a pan mixer. Next, a slump test for the concrete mixture was carried out. The concrete mixture was then used to produce 4 no. 100mm cubes and two 500 x 100 x 100 mm prisms based on table 1.1. Finally, the specimens were labeled and covered for curing. Sieving was also conducted on the fine and course aggregate to produce a sieving analysis chart.

Vibrating table | Hand Temper | Air cure | Water cure | Cube, CA1 | Prism, PA1 | Prism, PW1 | Cube, CW1 | Cube-7days, CW2 | Cube, CW3 |
Table 1.1 Conditions of produced cubes and prisms
Procedure for tests:
Our group were given a target 28 day compressive strength of 30 (N/mm2) and a slump test of 20mm. A compressive test was conducted on 1 of water cured cubes after 7 days and the rest of the cubes after 28 days. A PUNDIT, ERUDITE, and flexural test was conducted on both the prisms after 28 days. The Portable Ultrasonic Non Destructive Instrument Tester (PUNDIT) was used to obtain results for transit time, velocity and elastic modulus for the prisms. The Electronic Resonant Ultrasonic Direct Instrument (ERUDITE) was used to obtain the concrete’s first natural resonant frequency. A set of measurements were taken for both the PUNDIT and ERUDITE tests and

You May Also Find These Documents Helpful

  • Satisfactory Essays

    Panera Case Study

    • 183 Words
    • 1 Page

    Table 3 shows the flow value of the mixtures containing BA. It shows that flow value for the BA blended cement mortars were decreased with increase in the percentage of BA. The control mix (BAM 0) has a flow value of 147 mm [30]. The flow value of mixes BAM 5, BAM 10, BAM 15, BAM 20, BAM 25, and BAM 30 shows decrease of 146, 146, 145, 144, 143, and 142 mm respectively. BA requires more water for proper consistency when compared to that of ordinary Portland cement due to irregular shape with rough surfaces, high porous texture and absorptive in nature [5]. Increase in water demand of BA, decreases the flow value and resulted in poor workability. W/C ratio was kept same as 0.5 for all mixes. The flow value of BAM 30 reduced to 3.4 % due to…

    • 183 Words
    • 1 Page
    Satisfactory Essays
  • Powerful Essays

    For concrete is a mixture of coarse (stone or brick chips) and fine (generally sand or crushed stone) aggregates with a binder material like usually Portland cement. When mixed with a small amount of water, the cement hydrates to form microscopic opaque crystal lattices encapsulating and locking the aggregate into a rigid structure. Typical concrete mixes have high resistance to compressive stresses about 28 MPa. However, any appreciable tension (due to bending) will break the microscopic rigid lattice, resulting in cracking and separation of the concrete. For this reason, typical non-reinforced concrete must be well supported to prevent the development of tension.…

    • 7570 Words
    • 31 Pages
    Powerful Essays
  • Better Essays

    [Clips 5 & 6 – from Expedition Workshed - also show concrete cube test at failure point.] (Note that although the “design strength” of the concrete was 30 N/mm2, that is the expected strength at 30 days, whereas the specimens were tests at age of less than a week, and they had thus…

    • 997 Words
    • 4 Pages
    Better Essays
  • Good Essays

    Roman Pozzolanic Concrete

    • 680 Words
    • 3 Pages

    Concrete is a mixture made up of an aggregate, a binding agent and water. Typically the aggregate is gravel, sand or small stones. This is the filler that gives the final product its mass. The binding agent is what causes the mixture to set and harden. When the aggregate and binding agent are combined with water a thick mixture is created that can be poured into a form which then solidifies. In early civilization the binding agent was typically limestone powder or gypsum. The Romans discovered the use of pozzolana as a binding agent (Yegeul, n.d.). Pozzolana is a fine, sandy, volcanic ash which when used as a binding agent creates a strong durable concrete (Wikipedia, 2011, Pozzolana).…

    • 680 Words
    • 3 Pages
    Good Essays
  • Good Essays

    Concrete Lab Report

    • 1084 Words
    • 5 Pages

    Properties of concrete are governed not only by the properties of its ingredients (cement, water, sand, and coarse aggregate) but also, to a great extent, by the relative proportions of these ingredients. The proportions must be so selected as to produce a concrete mixture of desired workability, strength, durability, and economy.…

    • 1084 Words
    • 5 Pages
    Good Essays
  • Good Essays

    This is due to the fact that the concrete model used in ABAQUS has a concrete strength 26 MPa and the concrete strength for the experimental and design failure data is 22 MPa. By analysing the experimental data, the concrete strengths used in the tests varied from 22 MPa to 31 MPa. With this data it will be easy to get an adjustment factor that can be used for a more accurate prediction of the correct failure in the ABAQUS data. For the purpose of this study it is assumed that extrapolation can be used to get the correct failure strength for the ABAQUS failure data. Also, in the first test is could be seen that the failure force of ABAQUS was 29.37% lower than the average experimental force. With all this in consideration, it will be assumed that the ABAQUS failure force can be adjusted by a factor of 0.896. The adjusted failure force for ABAQUS in test two is 36.88 kN for a concrete strength of 22 MPa. By comparing the design failure data with the ABAQUS failure data, it can be seen that the ABAQUS failure data fails at a 25.44% higher force than the predicted failure force. By comparing the experimental failure data with the ABAQUS failure data, it can be seen that the ABAQUS failure data fails at a 41.09% lower force than the experimental failure…

    • 1551 Words
    • 7 Pages
    Good Essays
  • Good Essays

    Concrete Lab

    • 896 Words
    • 4 Pages

    Several mixtures of cement, aggregate, sand and water were mixed at different ratios to workability and compressive strength. The dry materials of the mixture were mixed and water was gradually added, the mixture was then placed in a cube and allowed to dry forming the concrete testing cube. Each of the four blocks containing different compositions of each material were then placed in a compressive testing machine and when each cube yielded, results were taken.…

    • 896 Words
    • 4 Pages
    Good Essays
  • Powerful Essays

    This report describes a compression test on concrete columns. The main aim of the tests was to illustrate the ultimate strength limit state of reinforced concrete columns in combined bending and compression and to demonstrate the influence of slenderness on the ultimate load capacity. Test methods are described. It was found that the concrete columns exhibited complicated behaviour, and had a squash load point of 342.7KN and moment at 0 KN.m, a decompression point of 227.75 KN and moment at 2.92 KN.m, a balanced point (nominal) of 58.46 KN and moment at 3.81KN.m, a pure bending point of 0 KN and moment at 2.86 KN.m, a balanced point (actual) of 42.26KN and moment at 3.86KN.m.…

    • 2017 Words
    • 9 Pages
    Powerful Essays
  • Powerful Essays

    References: Adewuyi, A.P., & Ola, B. F. (2005). Application of waterworks sludge as partial replacementfor cement in concrete production.…

    • 4288 Words
    • 32 Pages
    Powerful Essays
  • Better Essays

    The compressive, flexural, and tensile tests were performed several times with the concrete samples at an age of 7 days old and 28 days old to improve the accuracy of the results. The compressive, flexural, and tensile strength values were calculated and then averaged. The average compressive, flexural and tensile strength of the different concrete mixtures are shown in Table 1.…

    • 1620 Words
    • 7 Pages
    Better Essays
  • Good Essays

    It is the vital raw material needed to provide the structure required strength. For the reason, it is imperative to get the supreme quality concrete to ensure creating a strong foundation for the building structure. The manufacturer of concrete offering customized concrete mixture for construction purpose. They provide the concrete mixtures as per the client’s construction needs. They make use of the different proportion of the concrete components that include water, additives, cement, sand and stones that give the needed consistency, viscosity, and toughness for creating robust structures.…

    • 1010 Words
    • 5 Pages
    Good Essays
  • Good Essays

    Research Outline

    • 489 Words
    • 2 Pages

    Topic: Mussel Shells, Crab carapace and PVC as an alternate aggregate and filler in concrete making…

    • 489 Words
    • 2 Pages
    Good Essays
  • Good Essays

    Keywords: analysis; coarse aggregates; compressive strength; highstrength concrete; modulus of elasticity; normal-strength concrete; watercement ratio.…

    • 2667 Words
    • 8 Pages
    Good Essays
  • Satisfactory Essays

    Highway Elongation Test

    • 413 Words
    • 2 Pages

    * Aggregate shape, texture and grading have a significant effect on the performance of fresh concrete. Aggregate blends with well-shaped, rounded ,and…

    • 413 Words
    • 2 Pages
    Satisfactory Essays
  • Better Essays

    Concrete is widely used in constructing buildings, houses and other structures, but in order to have a strong structure there are factors to be considered. One of which is compressive strength, this is important to the structure especially if it is a high rise building and will be used commercially. The compressive strength of a concrete is important especially to the column of a structure because it resists compression force. Columns must have sufficient compressive strength to carry loads acting upon it.…

    • 8393 Words
    • 30 Pages
    Better Essays

Related Topics