Preview

Basic NEC Code Rules and Design Practice

Good Essays
Open Document
Open Document
1961 Words
Grammar
Grammar
Plagiarism
Plagiarism
Writing
Writing
Score
Score
Basic NEC Code Rules and Design Practice
BASIC NEC CODE RULES AND DESIGN PRACTICE

Wire Ampacity and Size

1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2, use NEC 310-16 for ampacity. This applies to not more than 3 phase conductors in 1 conduit.
Warning
Voltage Drop NEC 310-16 wire ampacity tables do not take into account voltage drop, only thermal limit. Overhead triplex, use 310-16 for wire ampacity.

Rule of Thumb

If circuit is loaded up to ampacity and distance to load is around 100 feet, then voltage drop will govern and will require larger wire size. If more than 3 phase wires are in one conduit, then wires must be derated according to Note 8, after Table 310-19 as follows:
TABLE 1
Number of Conductors Percent of Values in 310-16 *1-3 80 *4-6 80
7.24 70
25-42 60 43 and above 50

*If circuit is loaded up to 80% ampacity, then 6 phase wires can be put in one conduit. Neutral conductors supplying balanced loads do not have to be counted.
Note: Minimum Circuit size is #12 with 20 Amp CB.

Circuit Breaker Size 2. Maximum loading of any circuit breaker is 80% of rating for non-motor loads with exceptions as noted below. Breaker cannot be larger than ampacity of wire, except for motors and a few other loads.
TABLE 2
Load Maximum Circuit Breaker Size % of Current
Resistance Loads, Heat, Stoves, Toasters, Water Heater 125%
Lighting 125%
Motors except Hermetically Sealed 00-250% NEC 430-152
Motors Hermetically Sealed, Air conditioners 175%
And heat pumps
Welders 200%
MCP Breakers for Motors 125% or next larger size

Standard breaker sizes are listed Page 70-74, 240-6 NEC

Conduit Sizing
1. After circuits have been derated to get proper wire size use Table 3A if wires are all same size. Use Page 70-57"9, or Tables 4 and 5 if wires are all different size. Ground wires should be run with all branch

You May Also Find These Documents Helpful

  • Satisfactory Essays

    iLab Week4

    • 563 Words
    • 2 Pages

    current network, a new star topology network was created with 15 terminals and connected to the…

    • 563 Words
    • 2 Pages
    Satisfactory Essays
  • Satisfactory Essays

    Conduit is pipe. It can be metallic, nonmetallic, flexible, or rigid(depending upon local codes) and runs from a work area to a telecommunications room to the equipment room. One advantage of using conduit to hold the cables is that conduit may already exist in the building. A drawback to conduit is that it provides a finite amount of space to house cables. Conduit should be a maximum of 60 percent full. This margin leaves room for future growth. It is better to use conduit if it is already available and fireproofed.…

    • 675 Words
    • 2 Pages
    Satisfactory Essays
  • Good Essays

    Amath 250 notes

    • 36731 Words
    • 354 Pages

    1.3.6 Electrical circuits . . . . . . . . . . . . . . . . .…

    • 36731 Words
    • 354 Pages
    Good Essays
  • Satisfactory Essays

    IT 113 Cabling Exercise 2

    • 352 Words
    • 2 Pages

    2. Witch subsection of the ANSI/TIA-586-C standard would you reference for optical fiber cabling and component performance parameters?…

    • 352 Words
    • 2 Pages
    Satisfactory Essays
  • Satisfactory Essays

    Transmitting Bits

    • 2211 Words
    • 6 Pages

    Copper wire is used to power appliances which use more current. The difference is between signal circuits and power circuits. Signal circuits operate at extremely low current levels and use digital logic voltage levels (less than 5 VDC). Power circuits on the other hand require larger amounts of current to operate electrical devices such as motors, heating units, etc.…

    • 2211 Words
    • 6 Pages
    Satisfactory Essays
  • Satisfactory Essays

    i need help

    • 300 Words
    • 2 Pages

    2. How much power is consumed by a load drawing 5 A with 120 V across it?…

    • 300 Words
    • 2 Pages
    Satisfactory Essays
  • Powerful Essays

    Tirfir Coilomatic

    • 1477 Words
    • 6 Pages

    The Tirfor is a light duty winch, able to be used for many lifting and pulling jobs. This Service Technical Bulletin outlines the basic capacities and safe working procedures for the Tirfor T516 as used within this Service.…

    • 1477 Words
    • 6 Pages
    Powerful Essays
  • Good Essays

    move and handling

    • 772 Words
    • 2 Pages

    3.4 it is important to always check to identify risks straight away and try to correct it weather it is the wires are…

    • 772 Words
    • 2 Pages
    Good Essays
  • Good Essays

    All across this country on a daily basis construction jobs of varying size and types are built to varying specifications. Each specification is bound by clearly illustrated performance and workmanship standards within the national codes that are separated by division such as mechanical and electrical. If a buildings electrical system is installed to just a minimum standard it will be putting allot of people in harm’s way. Electricity is dangerous and explosions from things like an arc flash is something no one wants to see happen; but the fact is they do.. How can you be assured that the installation of a system in a given building or home is safe? The Code. The national electrical code gives the inspectors, contractors and the project crew…

    • 907 Words
    • 4 Pages
    Good Essays
  • Good Essays

    Numbers 1 to 4 below are not written out in your Lab Manual. They are provided here to help you do your calculations more clearly.…

    • 594 Words
    • 3 Pages
    Good Essays
  • Better Essays

    Discuss the effect on the magnitude of the force on a current-carrying conductor of variations in:…

    • 2998 Words
    • 12 Pages
    Better Essays
  • Good Essays

    testing ug cable

    • 1945 Words
    • 9 Pages

    This document proves the high and low voltage cable integrity after installation or jointing work is completed and before connection or reconnection to the PGCB Network. Such testing and commissioning will be undertaken by people, who are both qualified and authorized, and the relevant test results will be duly entered into the relevant test report form (refer to CEOF6022 and CEOF6023).…

    • 1945 Words
    • 9 Pages
    Good Essays
  • Good Essays

    Student

    • 1805 Words
    • 8 Pages

    KANIZSA-300 (DKG) - mast 42 m (137') max. hook load with 10 lines = 200 tons…

    • 1805 Words
    • 8 Pages
    Good Essays
  • Powerful Essays

    Anemometer Study

    • 2880 Words
    • 12 Pages

    No structural failures at design ultimate limit which is 50% more than design limit load. All loading will be added factor of 1.5 to meeting this requirement.…

    • 2880 Words
    • 12 Pages
    Powerful Essays
  • Satisfactory Essays

    Motor Control Panel

    • 370 Words
    • 2 Pages

    Control panels are UL Listed, labeled and constructed to meet the UL 508 standard. The pre-wired panel is…

    • 370 Words
    • 2 Pages
    Satisfactory Essays